YS-GJL-3 Building Component Fire Resistance Test Horizontal Furnace
Search

YS-GJL-3 Building Component Fire Resistance Test Horizontal Furnace

Scope of Application

【Operating Instructions】

    The thermal insulation efficiency test for steel structure fire retardant coatings is a newly added test item in the 2018 version of the national standard GB14907 "Steel Structure Fire Retardant Coatings"; it was not present in the 2002 version. Consequently, the Thermal Insulation Efficiency and Fire Resistance Limit Test Furnace became a key focus for equipment upgrades in related enterprises and institutions in 2019. According to GB14907-2018, the requirement for the thermal insulation efficiency deviation of indoor/outdoor steel structure fire retardant coatings is ±15%.



YS-GJL-3 Building Component Fire Resistance Test Horizontal Furnace

【Scope of Application】The thermal insulation efficiency test for steel structure fire retardant coatings is a newly added test item in the 2018 version of the national standard GB14907 "Steel Structure Fire Retardant Coatings"; it was not present in the 2002 version. Consequently, the Thermal Insulation Efficiency and Fire Resistance Limit Test Furnace became a key focus for equipment upgrades in related enterprises and institutions in 2019. According to GB14907-2018, the requirement for the thermal insulation efficiency deviation of indoor/outdoor steel structure fire retardant coatings is ±15%.

Introduction to the Test Furnace:The Steel Structure Fire Retardant Coating Thermal Insulation Efficiency and Fire Resistance Limit Test Furnace is a specialized instrument developed specifically for testing the fire resistance performance of steel structure fire retardant coatings. It is based on the technical specifications stipulated in National Standard GB14907-2018 "Steel Structure Fire Retardant Coatings" and GB/T9978-2008 (Sections 4 & 5, specifically 5.1 and 5.2).

The furnace features direct touch screen operation and control, eliminating the cumbersome process of connecting to a computer and installing software. The entire testing process is highly automated, offering easy operation and maintenance, with temperature errors strictly below national standard limits.

【Applicable Standards】

  • Design Standard: GB14907-2018 "Steel Structure Fire Retardant Coatings"

  • Reference Standard: GB/T9978-2008

【Instrument Features】

  1. Dual Control System: Supports both Touch Screen and Computer control with wireless connectivity. One computer can control multiple instruments simultaneously, and one instrument can be controlled by multiple computers.

  2. Automatic Fault Rejection: Automatically excludes faulty thermocouples from data processing.

  3. Full Automation: The entire testing process is fully automated.

  4. Real-time Curve Tracking: Automatically plots the test temperature curve in real-time.

  5. Pressure Tracking: Automatically plots the pressure curve.

  6. Auto-Cooling: Automatically initiates heat dissipation/ventilation upon test completion.

  7. Power Failure Protection: Features an anti-mistake power-off mode to prevent damage to the equipment caused by forced power cuts.

  8. Auto-Reignition: Automatically reignites the burner if the flame goes out during the test.

  9. Auto-Stop: Automatically stops the test when the set temperature is reached.

  10. Post-Test Ventilation: Automatically exhausts air to cool down after the test ends.

  11. Data Storage: Capable of storing more than 100 sets of data.

  12. High Precision: Temperature error is lower than the national standard requirements.

【Technical Specifications】

  1. Working Voltage: AC 220V ±10%, 50Hz; Power Consumption: 3KW

  2. Furnace Pressure Range: 0-100Pa; Pressure Control: 20±3Pa

  3. Air Flow Rate: 0-50m³/min; Measurement Accuracy: ≤±0.5 m³/min

  4. Fuel: No. 0 or No. -10 Diesel

  5. Test Temperature (Program Heating):

    • 60 min: Room Temp → 925℃

    • 120 min: Room Temp → 1050℃

    • 180 min: Room Temp → 1115℃

    • 240 min: Room Temp → 1150℃

    • 300 min: Room Temp → 1180℃

    • 360 min: Room Temp → 1210℃

  6. Equipment Accuracy:

    • Furnace Temperature Thermocouples: 4 units (High Precision)

    • Unexposed Surface Thermocouples: 2 units

    • Specimen Unexposed Surface Temperature: ±4℃

    • Control Mode: Selectable between Average Temperature Control or Individual Control.

  7. Temperature Sensor: Armored Nickel-Chromium/Nickel-Silicon (Type K) Thermocouple; Accuracy Class: Class II

  8. Heating Method: Fully automatic spray heater

  9. Cooling: Automatic exhaust ventilation for cooling after test completion.

  10. Storage: Capable of storing 100 sets of data.

  11. Timing Range: 0-360 min; Timing Accuracy: <±2s

  12. Specimen Size: 5005006mm

  13. Overall Dimensions: 1.6m * 1.6m * 1.6m

related product